The  traditional  source of heat  in industry, has been steam. However, higher  temperatures  of  steam require  higher  investment in the heat generation.  So  T&I  has  technical  understanding  with  Thermax,  a pioneer in the process heat industry, to supply Hot water generators.

Water boils when it’s vapour pressure equals the atmospheric pressure. Thus, when pressurised, water  can boil at temperatures above 100 °C. The hot water generator uses  this  principle to  heat  water as high as 140 °C  or beyond  without  changing  its  liquid  state.  This  water  is transferred  in  a  pressurised   closed   loop  system  to  the  point  of application.





#  High quality high temperature seamless tubes/coils
 #  
3-pass thermally efficient heater
 #  Efficient combustion system
 #  Fully automatic control system
 #  All safety instruments and controls are provided
 #  Very compact and occupies minimum floor area

 

 



 
MODEL
 
UNIT
ATH-02
ATH-03
ATH-04
ATH-06
ATH-10
ATH-15
A) OPERATING DATA
HEAT OUTPUT
Kcal/Hr
2,00,000
3,00,000
4,00,000
6,00,000
10,00,000
15,00,000
OUTLET TEMPERATURE (Max)
°C
140
MAX HEAD AVAILABLE AT HEATER OUTLET
MLC
20
BURNER MODULATION  
ON/OFF                      STEPLESS

B) THERMAL DATA

EFFICIENCY
%
90 ± 2
                                                            RATED FUEL CONSUMPTION (ON N.C.V.)
L.D.O. : 10,050 Kcal/Kg
Kg/Hr
22.2
33.2
44.3
66.3
111
166
H.S.D. : 10,800 Kcal/Kg
Kg/Hr
20.6
31.0
41.2
62.0
103
155
F.O. : 9650 Kcal/Kg
Kg/Hr
23
35
46
69
115
173
C) ELECTRICAL DATA
CIRCULATION PUMP
KW
2.2
3.7
3.7
5.5
7.5
9.3
MAKE UP PUMP
KW
1.1
1.1
1.1
1.1
1.1
1.1
FUEL PUMP
KW
   Common Motor for Fan and Fuel Pump   0.75         1.1
COMBUSTION AIR FAN
KW
1.5
1.5
2.2
3.7
7.5
11.0
OIL PREHEATER (For F.O. unit)
KW
3.0
3.0
3.0
6.0
9.0
12.0
CONTROL PANEL
KW
0.2
0.2
0.2
0.7
0.75
0.5
TOTAL LDO / HSD
KW
5.0
6.5
7.2
11.0
17.6
31.0
F.O.
KW
8.0
9.5
10.2
17.0
23.4
43.0
D) OTHER DATA                                                                              VERTICAL UNIT
OVERALL DIMENSIONS  
Height(mm)
2260
2335
2805
3260
3340
3950
 
Length (mm)
1600
1595
1900
2140
2610
3015
 
Width (mm)
1030
1175
1860
1975
1975
2255
WEIGHT (APPROX)
Kgs
1125
1200
2325
2830
3000
4800
FLOW RATE
M3 / Hr
9
13
17
25
42
63
POWER SUPPLY REQUIRED       
415 V ± 6%, 50 HZ ± 3%,  3 PHASE AC

 #  Wide capacity range from 1 lakh Kcal/hr to 2 million Kcal/hr
 # 
Multi-fuel firing system
 #  Less Power and fuel consumption
 #  No Boiler regulation required
 #  
Less initial investment compared to boilers
 #  Requires smaller piping system, since specific heat of water is much higher
 #  No fire hazards, since working media is water